Static Pressure vs Total Pressure (with Practical Examples in mmWG and m³/sec)
Understanding Static Pressure (SP) and Total Pressure (TP) is fundamental in fan engineering, system design, and troubleshooting. These terms are often misunderstood, yet they directly determine fan selection, power consumption, airflow performance, and system resistance.
1. Static Pressure (SP)
Static Pressure is the pressure required to overcome resistance in the system.
It is the pressure that pushes air or gas against:
ducts
bends
dampers
bag filters
cyclones
scrubbers
furnace resistance
stacks
It does not include velocity energy.
Think of static pressure as:
“The force needed to push air through obstacles.”
Unit: mmWG (millimeter water gauge)
Practical Example 1 – Bag Filter System
Suppose a dust extraction system has:
duct resistance = 80 mmWG
bag filter pressure drop = 120 mmWG
bends/dampers = 40 mmWG
chimney loss = 30 mmWG
Total static pressure:
SP = 80 + 120 + 40 + 30
SP = 270 mmWG
Meaning:
The fan must generate at least 270 mmWG static pressure to move air through the system.
Water analogy
Imagine water flowing through a pipe with many restrictions.
Static pressure = pressure needed to overcome restrictions.
Same in air systems.
2. Velocity Pressure (VP)
Moving air has kinetic energy.
That kinetic energy creates velocity pressure.
Formula:
VP = V² / 16.34
(where V in m/s approximately for mmWG context)
This pressure exists only because air is moving.
If airflow stops:
Velocity pressure becomes zero.
Example:
Air velocity = 20 m/s
VP = 20² / 16.34
= 400 / 16.34
= 24.5 mmWG
3. Total Pressure (TP)
Total pressure is:
Static Pressure + Velocity Pressure
Formula:
TP = SP + VP
This is the complete energy the fan imparts to the air.
Example:
Static pressure = 270 mmWG
Velocity pressure = 24.5 mmWG
Total pressure:
TP = 270 + 24.5
= 294.5 mmWG
Meaning:
The fan actually develops 294.5 mmWG total energy, but only 270 mmWG is available to overcome system resistance.